Static secondary ion mass spectrometry investigation of corrosion inhibitor Irgamet®39 on copper surfaces treated in power transformer insulating oil
Static secondary ion mass spectrometry investigation of corrosion inhibitor Irgamet®39 on copper surfaces treated in power transformer insulating oil
复制标题
DOI:
10.1016/j.corsci.2015.05.046
复制
发表时间:
2015-09
影响因子:
8.3
通讯作者:
M. Facciotti;P. Amaro;Richard C. D. Brown;P. Lewin;J. Pilgrim;G. Wilson;P. Jarman;I. W. Fletcher
中科院分区:
文献类型:
--
作者:
M. Facciotti;P. Amaro;Richard C. D. Brown;P. Lewin;J. Pilgrim;G. Wilson;P. Jarman;I. W. Fletcher
Static secondary ion mass spectrometry was used to study the corrosion inhibitor Irgamet®39 on the surface of copper treated in insulating oils and the effect of temperature changes, by means of temperature programmed desorption experiments under vacuum, on metal coverage. Four commercial oils, both corrosive and non-corrosive, showed no significant influence on the stability of the tolyltriazole layer and the energy of its main desorption event from copper was calculated around 100 kJ mol−1. Finally, an example of ion imaging as diagnostic tool to track the distribution of corrosion inhibitor and by-products in decommissioned or failed power transformers is described.