Impacts of Hysteresis and Magnetic Couplings on the Stability Domain of Ferroresonance in Asymmetric Three-Phase Three-Leg Transformers

Impacts of Hysteresis and Magnetic Couplings on the Stability Domain of Ferroresonance in Asymmetric Three-Phase Three-Leg Transformers
复制标题

DOI:
10.1109/tec.2010.2088400
复制
发表时间:
2011-06
影响因子:
4.9
通讯作者:
P. Moses;M. Masoum;H. Toliyat
P. Moses;M. Masoum;H. Toliyat
中科院分区:
工程技术1区
文献类型:
--
作者:
P. Moses;M. Masoum;H. Toliyat

文献摘要

被引文献

相似文献

This paper investigates the stability domain of ferroresonance in asymmetric three-phase three-leg transformers considering magnetic couplings and hysteresis effects of the core. A newly developed and accurate time-domain transformer model capable of simulating dynamic and transient operating conditions is implemented in this study. The model is based on electromagnetic circuit theory and considers dynamic hysteresis effects (major and minor loops) as well as core topology, asymmetry, and magnetic flux cross-coupling interactions of the core legs. Unbalanced switching with series and shunt capacitances, which is known to increase the risk of ferroresonance, is studied with the developed model. The validity of the model under ferroresonant conditions is confirmed by comparisons with extensive experimental data. The main contribution is a new analysis of (a)symmetric three-phase transformer ferroresonance behavior with an accurate core model capable of predicting ferroresonance modes.