Development and test of resistive superconducting fault current limiter; acting time and its recovery conditions
Development and test of resistive superconducting fault current limiter; acting time and its recovery conditions
复制标题
电阻性超导故障限流器的研制与测试;
DOI:
10.1088/1742-6596/507/3/032004
复制
发表时间:
2014
期刊:
影响因子:
--
通讯作者:
E. Ruppert
中科院分区:
文献类型:
--
作者:
C. Baldan;L. C. Guedes;J. Lamas;C. Y. Shigue;E. Ruppert
Resistive-type of superconducting fault current limiters (RSFCL) have been developed for medium voltage class aiming to operate at 1 MVA power capacity and short time recovery (< 2 s). A RSFCL in form of superconducting modular device was designed and constructed using 50 m-length of YBCO coated conductor tapes for operation under 1 kV / 1 kA and acting time of 0.1 s. In order to increase the acting time the RSFCL was combined with an air-core reactor in parallel to increase the fault limiting time up to 1 s. The tests determined the electrical and thermal characteristics of the combined resistive/inductive protection unit. The combined fault current limiter reached a limiting current of 583 A, corresponding to a limiting factor of 3.3 times within an acting time of up to 1 s.