Jet REMPI for the detection of trace gas compounds in complex gas mixtures : a tool for kinetic research and incinerator process control
Jet REMPI for the detection of trace gas compounds in complex gas mixtures : a tool for kinetic research and incinerator process control
复制标题
Jet REMPI 用于检测复杂气体混合物中的痕量气体化合物:动力学研究和焚烧炉过程控制的工具
DOI:
--
复制
发表时间:
1996
期刊:
影响因子:
--
通讯作者:
H. Grotheer
中科院分区:
文献类型:
--
作者:
H. Oser;R. Thanner;H. Grotheer
Flame optimization in incinerators is achievable by feedback control via kinetic modelling and on-line monitoring. On-line monitoring for process control requires a fast, selective and sensitive analytical device. In this paper a REM PI (Resonance Enhanced Multi Photon Ionization) mass spectrometer is presented which combines high sensitivity with very low cross-sensitivity. Consequently, it should be a valuable tool for both kinetic research and for on-line investigation. The sensitivity of the instrument has been increased by shifting the ionization regime close to the continuous portion (“jet”) of the sample beam as opposed to the more conventional ionization within the molecular beam. A further gain in sensitivity was achieved by increasing the ionization volume which was made possible by a complete re-design of the ion source. A very low base-line level is achieved by using a geometry which prevents secondary ionization by the collision of ions/electrons with surfaces. These improvements result in an...