Laboratory Tests Study on the Power Dissipation Characteristics of Conductor Self-Damping and Aeolian Vibration Dampers
Laboratory Tests Study on the Power Dissipation Characteristics of Conductor Self-Damping and Aeolian Vibration Dampers
复制标题
DOI:
10.4028/www.scientific.net/amm.29-32.2290
复制
发表时间:
2010-08
期刊:
影响因子:
--
通讯作者:
Yuankun Chen;Li Li-Li;Kun Ye;P. Yin
中科院分区:
文献类型:
--
作者:
Yuankun Chen;Li Li-Li;Kun Ye;P. Yin
In this paper, laboratory tests on conductor aeolian vibration were designed and carried out, through which the power dissipation characteristics of conductor self-damping and wire dampers(bretelles) were investigated. In addition, the theoretical method was established to estimate the power dissipated by wire damper. The results show that conductor tension and vibration frequency have great influences on its self-damping property; furthermore, the results present that the natural frequency of wire damper is related with its length and the length of wire damper has significant impact on its anti-vibration effect. The theoretical method for calculating the power dissipated by wire damper was verified to be reliable by the test results. These conclusions can provide references for the research and anti-vibration design of transmission line engineering.