Analysis of Dynamic Arc Parameters for Vacuum Circuit Breaker under Short-circuit Current Breaking
Analysis of Dynamic Arc Parameters for Vacuum Circuit Breaker under Short-circuit Current Breaking
复制标题
DOI:
10.1109/asemd.2018.8558979
复制
发表时间:
2018-04
期刊:
影响因子:
--
通讯作者:
Hai Chen;Xiaoming Liu;Longnv Li;Yixiong Liu;Yaqian Zhang;Yunfei Huang
中科院分区:
文献类型:
--
作者:
Hai Chen;Xiaoming Liu;Longnv Li;Yixiong Liu;Yaqian Zhang;Yunfei Huang
For observing the vacuum arc behavior variation, the experiment platform for a 40.5kV/31.5kA/2500A vacuum circuit breaker (VCB) was established and the variation of the arc voltage and arc current was obtained under the typical shortcircuit current breaking condition. Moreover, for analyzing the dielectric recovery characteristics and the interrupting capability for the VCB, the dynamic arc energy, the arc resistance and the arcing time under different short-circuit current breaking conditions was illustrated and analyzed.