Response to the Intermediate Source Effect and Mutual Coupling of the Distance Relay with CMC 356 Test Set
Response to the Intermediate Source Effect and Mutual Coupling of the Distance Relay with CMC 356 Test Set
复制标题
使用 CMC 356 测试仪响应距离继电器的中间源效应和互耦
DOI:
10.1109/urucon53396.2021.9647147
复制
发表时间:
2021
期刊:
影响因子:
--
通讯作者:
F. Quizhpi
中科院分区:
文献类型:
--
作者:
Joel Agila;Fernando Pina;F. Quizhpi
Distance relay faces problems that affect impedance measurement, including the infeed effect on remote buses and mutual coupling of parallel lines. These effects may cause the distance protection to fail to distinguish the fault, or to detect it in other protection zones. The paper addresses techniques to adjust the distance relay for such effects, using protection zones 1 and 2, and a method to compensate for the effect of mutual coupling of parallel lines; different from the conventional technique is proposed. The suggested settings satisfy the predicted results in simulation and testing with the CMC 356 Omicron equipment.