VSC transmission operating under unbalanced AC conditions - analysis and control design
VSC transmission operating under unbalanced AC conditions - analysis and control design
复制标题
DOI:
10.1109/tpwrd.2004.835032
复制
发表时间:
2005-02
影响因子:
4.4
通讯作者:
Lie Xu;B. Andersen;P. Cartwright
中科院分区:
文献类型:
--
作者:
Lie Xu;B. Andersen;P. Cartwright
This work presents an analysis and a new control design of a voltage-source converter (VSC) transmission system operating under unbalanced network conditions. The system is analyzed in the positive and negative synchronous reference frames. The proposed control strategy contains a main controller and an auxiliary controller. The main controller is implemented in the positive d-q frame using decoupling control without involving positive/negative-sequence decomposition. The auxiliary controller is implemented in the negative-sequence d-q frame using cross-coupling control of negative-sequence current. Simulation results using the SIMULINK power system blockset show good performance of the proposed control strategy for a 300-MW 300-kV dc VSC transmission system during both balanced conditions and unbalanced conditions as may be caused by a solid single-phase-to-ground fault.