Performance evaluation of a two-stage CO2 cycle with gas injection in the cooling mode operation
Performance evaluation of a two-stage CO2 cycle with gas injection in the cooling mode operation
复制标题
DOI:
10.1016/j.ijrefrig.2008.07.008
复制
发表时间:
2009
期刊:
影响因子:
--
通讯作者:
Honghyun Cho;Changhyun Baek;Chasik Park;Yongchan Kim
中科院分区:
文献类型:
--
作者:
Honghyun Cho;Changhyun Baek;Chasik Park;Yongchan Kim
The cooling performance and reliability of a transcritical CO2cycle can be significantly improved by using a multi-stage compressor with gas injection because the CO2cycle has a large pressure difference across a compressor. The objective of this study is to investigate the performance and operating characteristics of a two-stage CO2cycle with gas injection. In this study, the performances of a two-stage CO2cycle with gas injection (called as “two-stage gas injection cycle”) were measured as the amount of refrigerant charge, first- and second-stage compressor frequencies, and first- and second-stage EEV openings were varied in the cooling mode operation. The cooling COP of the two-stage gas injection cycle was maximally enhanced by 16.5% over that of the two-stage non-injection cycle in the experiments. In addition, when the first- and second-stage EEV openings were increased, the compression ratio decreased and this in turn, improved the cooling COP of the two-stage gas injection cycle. However, when the first-stage EEV opening was increased, the mass flow rate through the evaporator decreased, and this in turn, decreased the cooling capacity of the two-stage gas injection cycle. Therefore, in the two-stage gas injection cycle, an optimum control of both EEV openings is required.