Manufacturing and testing of MCP 2212 bifilar coils for a 10 MVA fault current limiter
Manufacturing and testing of MCP 2212 bifilar coils for a 10 MVA fault current limiter
复制标题
用于 10 MVA 故障限流器的 MCP 2212 双线线圈的制造和测试
DOI:
10.1109/tasc.2003.812954
复制
发表时间:
2003
期刊:
影响因子:
--
通讯作者:
J. Bock
中科院分区:
文献类型:
--
作者:
S. Elschner;F. Breuer;M. Noe;T. Rettelbach;H. Walter;J. Bock
A very promising option within the German 10 kV/10 MVA superconducting fault current limiter project CURL 10 is melt cast processed (MCP-) BSCCO 2212 bulk material. With tube shaped samples cut to bifilar coils and contacted in series, the required long lengths (160 m per phase) can easily be achieved. At the operating temperature of T=65 K the critical current density is near 4000 A/cm/sup 2/ and the voltage under limiting conditions reaches E/sub p/=0.5 V/cm. The contribution describes the design, manufacturing and testing of the superconducting components. In particular the development and characterization of a suitable electrical shunt is focused. Finally the finished components are characterized with respect to electrical homogeneity and under various limiting conditions. It could be confirmed that the single components each meet all the requirements defined within the project.