Experimental analysis of R22 and R407c flow through electronic expansion valve
Experimental analysis of R22 and R407c flow through electronic expansion valve
复制标题
DOI:
10.1016/j.enconman.2005.05.005
复制
发表时间:
2006-03
影响因子:
10.4
通讯作者:
Chuan Zhang;Shanwei Ma;Jiangpin Chen;Zhi-jiu Chen
中科院分区:
文献类型:
--
作者:
Chuan Zhang;Shanwei Ma;Jiangpin Chen;Zhi-jiu Chen
The objective of this study is to present test results and to develop a dimensionless correlation on the basis of experimental data to predict the mass flow rate of R22 and its alternative refrigerant R407c through an electronic expansion valve (EEV). The mass flow rate was measured at a series of condensing temperatures, evaporating temperatures and degrees of subcooling at the EEV inlet with five opening setting degrees of the EEV. The experimental results were analyzed, and it was found that the operation condition, flow area and the thermophysical properties of the refrigerant would affect the mass flow rate through the EEV. A new correlation based on the Buckingham π theorem was developed to predict the mass flow rate of refrigerants through the EEV. The relative deviations of the predicted value by using this correlation are from −10.74% to 9.26% for R22 and from −14.20% to 22.10% for R407c. The average deviations and standard deviations are −0.79% and 5.02% for R22 and 0.67% and 8.08% for R407c, respectively. The relative deviation was analyzed in terms of the operation condition and flow area of the EEV. This correlation can be used to predict the mass flow rate through EEVs whose largest flow area is less than 2.544mm2.