An Improved Approach for AC-DC Power Flow Calculation With Multi-Infeed DC Systems
An Improved Approach for AC-DC Power Flow Calculation With Multi-Infeed DC Systems
复制标题
DOI:
10.1109/tpwrs.2010.2068579
复制
发表时间:
2011-05
影响因子:
6.6
通讯作者:
Chongru Liu;Boming Zhang;Yunhe Hou;Felix F. Wu;Yingshang Liu
中科院分区:
文献类型:
--
作者:
Chongru Liu;Boming Zhang;Yunhe Hou;Felix F. Wu;Yingshang Liu
An improved approach based on sequential method for the AC-DC power flow calculation is proposed in this paper. This approach solves the convergence problem caused by voltage violations at AC buses during the power flow calculation for the DC subsystems. The convergence property can be significantly improved by adjusting the converter transformer tap position flexibly. In order to adjust the tap position of the converter transformer flexibly, three mainly modifications are proposed. Firstly, the equations for whole DC systems are decoupled into individual DC systems so as to easily figure out which DC system's tap position needs adjustment. Secondly, the tap ratio of a converter transformer is selected as an alternative state variable to replace the cosine of the control angle when necessary. Thirdly, the Newton-Raphson method is utilized to solve DC subsystems instead of the method using the linear equations. Furthermore, a theoretical analysis of the advantages of the proposed approach is also presented. Numerical simulations and practical applications show that the proposed approach meet the requirement of different system operating conditions and has advantages in terms of convergence and speed. The proposed approach has been successfully integrated into the Energy Management System (EMS) for China Southern Power Grid.