Partial discharge investigation of a power transformer using wireless wideband radio-frequency measurements
Partial discharge investigation of a power transformer using wireless wideband radio-frequency measurements
复制标题
DOI:
10.1109/tpwrd.2005.848438
复制
发表时间:
2006-01-01
影响因子:
4.4
通讯作者:
Glover, IA
中科院分区:
文献类型:
--
作者:
Moore, PJ;Portugues, IE;Glover, IA
The remote detection of a transformer internal partial discharge (PD) has been demonstrated using mobile wideband radio-frequency receiving equipment. The PD is externally detectable due to coupling within the transformer tank, causing impulsive signals to be radiated from external connections. A wideband direction-finding technique using a four-antenna array has shown the source of the radiation to be the tertiary winding connections; the radiated impulse has characteristics typical of this method of emission. No other external site of radiation from the transformer was detected. Due to the lack of coupling to the primary and secondary windings, it is believed that the PD is present between the tertiary windings and the core.