Ground-Fault Feeder Detection With Fault-Current and Fault-Resistance Measurement in Mine Power Systems
Ground-Fault Feeder Detection With Fault-Current and Fault-Resistance Measurement in Mine Power Systems
复制标题
DOI:
10.1109/tia.2008.916744
复制
发表时间:
2008-03
影响因子:
4.4
通讯作者:
Xiangjun Zeng;K. Li;W. L. Chan;Sheng Su;Yuanyuan Wang
中科院分区:
文献类型:
--
作者:
Xiangjun Zeng;K. Li;W. L. Chan;Sheng Su;Yuanyuan Wang
Many mine power systems operate with a floating neutral or are high-resistance grounded, and earth fault current is no more than a few tens of amperes. Traditional earth-fault-detection methods based on zero-sequence current have poor sensitivity in this case. For improvement, a fault-detection scheme with fault-current and fault-resistance measurement is presented in this paper, which is capable of detecting high-impedance ground faults. The scheme has been verified by electromagnetic-transient-program simulation, and a fault-detection prototype has been developed and tested in the laboratory. Results show that the scheme has high sensitivity and robustness.