Ground-Fault Feeder Detection With Fault-Current and Fault-Resistance Measurement in Mine Power Systems

Ground-Fault Feeder Detection With Fault-Current and Fault-Resistance Measurement in Mine Power Systems
复制标题

DOI:
10.1109/tia.2008.916744
复制
发表时间:
2008-03
影响因子:
4.4
通讯作者:
Xiangjun Zeng;K. Li;W. L. Chan;Sheng Su;Yuanyuan Wang
Xiangjun Zeng;K. Li;W. L. Chan;Sheng Su;Yuanyuan Wang
中科院分区:
工程技术2区
文献类型:
--
作者:
Xiangjun Zeng;K. Li;W. L. Chan;Sheng Su;Yuanyuan Wang

文献摘要

被引文献

相似文献

许多矿井电力系统采用浮动中性点或高电阻接地,接地故障电流不超过几十安培。传统的基于零序电流的接地故障检测方法在这种情况下灵敏度较差。针对此问题,本文提出了一种结合故障电流和故障电阻测量的故障检测方案,该方案能够检测高阻抗接地故障。该方案已通过电磁暂态程序仿真验证,并在实验室开发和测试的故障检测原型。结果表明,该方案具有较高的灵敏度和鲁棒性.
Many mine power systems operate with a floating neutral or are high-resistance grounded, and earth fault current is no more than a few tens of amperes. Traditional earth-fault-detection methods based on zero-sequence current have poor sensitivity in this case. For improvement, a fault-detection scheme with fault-current and fault-resistance measurement is presented in this paper, which is capable of detecting high-impedance ground faults. The scheme has been verified by electromagnetic-transient-program simulation, and a fault-detection prototype has been developed and tested in the laboratory. Results show that the scheme has high sensitivity and robustness.