被引文献

相似文献

本文讨论了三相直流电抗器型故障限流器(FCL)在短路测试中的运行特性。该类型整箱由变压器组成。二极管和超导线圈。本文采用Nb-Ti材料制成的超导线圈、低Tc SMES磁体,实验电路的电源系统为400 V/7 A级。这是开发其高压输电线路应用能力的初步步骤。实验结果是,当变压器匝数比为1和2时,限制率分别约为77%和90%。
This paper deals with the operational characteristics of a three-phase DC reactor type fault current limiter (FCL) at a short-circuit test. This type FCL consists of transformers,. diodes, and a superconducting coil. In this paper, a superconducting coil, low-Tc SMES magnet, is made of Nb-Ti and the power system of the experimental circuit is 400 V/7 A class. This is a preliminary step to develop its faculties for applications to high voltage transmission line. As the results of the experiment, the values are referred to the limitation rate about 77% and 90% when the turns ratio of transformer was 1 and 2, respectively.