AN ANALYSIS OF HARMONIC DISTURBANCES IN DISTRIBUTION SYSTEMS CAUSED BY GRID-CONNECTED INVERTERS: EXPERIMENTAL VERIFICATION OF HIGH-ORDER HARMONIC RESONANCE
AN ANALYSIS OF HARMONIC DISTURBANCES IN DISTRIBUTION SYSTEMS CAUSED BY GRID-CONNECTED INVERTERS: EXPERIMENTAL VERIFICATION OF HIGH-ORDER HARMONIC RESONANCE
复制标题
DOI:
--
复制
发表时间:
2019
期刊:
影响因子:
--
通讯作者:
N. Okada;Kenichiro
中科院分区:
文献类型:
--
作者:
N. Okada;Kenichiro
Harmonic disturbances caused by the high-order harmonics (2kHz ~ 9kHz) of grid-connected inverters were observed in the medium-voltage distribution systems which host a large amount of distributed generations. It was demonstrated by the previous computer simulations that voltage harmonics may exceed the suppression level of the distribution system even if the current harmonics of the inverters satisfy the suppression level recommended in the grid-code. It is required to validate the disturbance by the experiment along with clarifying its condition and mechanism. This research investigates harmonic characteristics of the grid-connected inverters by the experiment under different switching frequency and grid configurations. Large harmonic voltage is observed across the shunt capacitor if the series resonant frequency of the grid-side impedance coincides with the switching frequency of the inverter. Since the grid-side impedance decreases at the series resonant frequency, harmonic current leaks from the harmonic filter, and then it flows into the shunt capacitor. The series resonant frequency is influenced by the grid-side impedance, which can be calculated by the circuit parameters.