Comparison of contact measurement and free-space radiation measurement of partial discharge signals
Comparison of contact measurement and free-space radiation measurement of partial discharge signals
复制标题
DOI:
10.1109/iconac.2015.7313955
复制
发表时间:
2015-09
期刊:
影响因子:
--
通讯作者:
A. Jaber;P. Lazaridis;Yong Zhang;D. Upton;H. Ahmed;U. Khan;B. Saeed;P. Mather;M. F. Vieira;R. Atkinson;M. Judd;I. Glover
中科院分区:
文献类型:
--
作者:
A. Jaber;P. Lazaridis;Yong Zhang;D. Upton;H. Ahmed;U. Khan;B. Saeed;P. Mather;M. F. Vieira;R. Atkinson;M. Judd;I. Glover
Two partial discharge (PD) measurement techniques, a contact measurement technique (similar to the IEC 60270 standard measurement) and a free-space radiation (FSR) measurement technique, are compared for the case of a floating electrode PD source. The discharge pulse shapes and PD characteristics under high voltage DC conditions are obtained. A comparison shows greater similarity between the two measurements than was expected. It is inferred that the dominant mechanism in shaping the spectrum is the band-limiting effect of the radiating structure rather than band limiting by the receiving antenna. The cumulative energies of PD pulses in both frequency and time domains are also considered.