Investigation on High-Performance Single-Stage GM-Type Pulse Tube Cooler
Investigation on High-Performance Single-Stage GM-Type Pulse Tube Cooler
复制标题
DOI:
--
复制
发表时间:
2004
期刊:
影响因子:
--
通讯作者:
Jia Yan-long;Chen Guo-bang
中科院分区:
文献类型:
--
作者:
Jia Yan-long;Chen Guo-bang
Experimental investigation on DC flow suppression and refrigeration characteristics of a high-performance single-stage GM-type pulse tube cooler has been undertaken. The influence of DC flow induced by the introduction of double-inlet on the refrigeration performance of the cooler is experimentally examined. Two parallel-placed needle valves with opposite flow direction called double-valved configuration, instead of conventional single-valved configuration as the double-inlet is successfully used in this experiment to reduce the DC flow. With a double-valved configuration, 18.4 K and 14.7 K (minimum temperature) are reached driven by RW2 and CP4000 compressor, respectively, and 11.5 W and 29.5 W (cooling power) at 30 K are obtained as well.