Meta-analysis of indoor temperatures in new-build housing

Meta-analysis of indoor temperatures in new-build housing
复制标题

DOI:
10.1080/09613218.2016.1226610
复制
发表时间:
2017-02
影响因子:
3.9
通讯作者:
Gráinne McGill;T. Sharpe;L. Robertson;Rajat Gupta;Ian Mawditt
Gráinne McGill;T. Sharpe;L. Robertson;Rajat Gupta;Ian Mawditt
中科院分区:
工程技术3区
文献类型:
--
作者:
Gráinne McGill;T. Sharpe;L. Robertson;Rajat Gupta;Ian Mawditt

文献摘要

被引文献

相似文献

摘要尽管人们越来越担心经济过热,但缺乏证据表明这一问题的严重性,特别是在当代英国的住房问题上。本文介绍了在选定的低能耗住宅室内温度的荟萃分析的结果。对19个示范项目(2012- 2014年)60个住宅每隔5分钟记录的温度数据进行了整理和分析,以调查过热的普遍性。调查结果表明,夏季温度很高,27%的客厅在8月份超过28°C。根据英国建筑服务工程师学会(CIBSE)的标准,每年有5%的居住时间超过25°C,57%的卧室和75%的客厅被归类为过热。总体而言,30%的客厅超过了自适应舒适阈值,即> 3%的占用时间ΔT ≥ 1 K。结果表明,通风和室内温度之间的基本关系。在机械通风热回收(MVHR)住宅中观察到的较高的最低和平均夏季温度(p < 0.05)和较低的温度范围(p < 0.001)表明需要更加注意在密闭住宅中提供足够的夏季通风。结果表明,在示范住房过热的高患病率,表明需要更大的努力,以确保有效实施的战略,以尽量减少过热和改善低能耗家庭的通风。
ABSTRACT Despite growing concerns about overheating, a lack of evidence exists on the scale of the problem, particularly in contemporary UK housing. This paper presents the results of a meta-analysis of indoor temperatures in selected low-energy housing. Temperature data recorded at five-minute intervals in 60 dwellings across 19 demonstration projects (2012–14) were collated and analysed to investigate the prevalence of overheating. Findings evidence high summertime temperatures, with 27% of living rooms exceeding 28°C during August. Based on the Chartered Institution of Building Services Engineers (CIBSE) threshold of 5% annual occupied hours > 25°C, 57% of bedrooms and 75% of living rooms were classified as having overheated. Overall, 30% of living rooms exceeded the adaptive comfort threshold of > 3% occupied hours ΔT ≥ 1 K. The results suggest a fundamental relationship between ventilation and indoor temperatures. The higher minimum and average summertime temperatures observed in mechanical ventilation with heat recovery (MVHR) homes (p < 0.05) and lower temperature range (p < 0.001) suggest the need for greater attention to adequate summertime ventilation provision in airtight homes. The results demonstrate a high prevalence of overheating in exemplary housing, indicating the need for greater efforts to ensure the effective implementation of strategies to minimize overheating and improve ventilation in low-energy homes.