Current chopping phenomena of medium voltage circuit breakers
Current chopping phenomena of medium voltage circuit breakers
复制标题
DOI:
10.1109/t-pas.1977.32317
复制
发表时间:
1977
期刊:
影响因子:
--
通讯作者:
M. Murano;Satoru Yanabu;H. Ohashi;H. Ishizuka;T. Okazaki
中科院分区:
文献类型:
--
作者:
M. Murano;Satoru Yanabu;H. Ohashi;H. Ishizuka;T. Okazaki
The authors have investigated the relation between the circuit conditions and the chopping current values of various types of circuit breakers, including MOCB(Minimum Oil CB), VCB(Vacuum CB), ABCB (Air Blast CB) and GCB (SF6 Puffer CB). Excepting VCB, each breaker chopping current increases with increase of the parallel capacitance to the breaker, but it decreases when a series resistance is connected to this capacitance. Concerning to MOCB, ABCB and GCB, it was found that the phenomena just before current chopping quite resemble each other, while as for VCB, it differs from others completely. These were investigated throughly from experiments and theory.