Coordinated control of interarea oscillation in the China Southern power grid
Coordinated control of interarea oscillation in the China Southern power grid
复制标题
DOI:
10.1109/tpwrs.2006.873116
复制
发表时间:
2006-05
影响因子:
6.6
通讯作者:
Mao Xiao-ming;Z. Yao;Guan Lin;Wu Xiaochen
中科院分区:
文献类型:
--
作者:
Mao Xiao-ming;Z. Yao;Guan Lin;Wu Xiaochen
The China Southern Power Grid (CSG) interconnects four provincial power grids: Guangdong, Guangxi, Yunnan, and Guizhou. It is the only ac/dc hybrid grid in China with dual ac/dc transmission corridors in parallel. The practical high-voltage direct current (HVDC) control scheme of the CSG and its modeling is first presented. Both the stability and small-signal analysis environments of 2005 CSG are established using a commercial software package. Interarea oscillatory modes among the four provincial power grids are then investigated. On the basis of modal analysis, a hierarchical optimization scheme is implemented for the parameter setting of selected power system stabilizers (PSS) and HVDC damping controllers. Digital simulations show that proper coordination of the PSS and HVDC modulation controllers can effectively suppress the interarea oscillation in large-scale ac/dc hybrid power systems under a wide range of operating conditions.