Corrosive Sulfur Induced Failures in Oil-Filled Electrical Power Transformers and Shunt Reactors
Corrosive Sulfur Induced Failures in Oil-Filled Electrical Power Transformers and Shunt Reactors
复制标题
DOI:
10.1109/tpwrd.2008.2005369
复制
发表时间:
2009-06
影响因子:
4.4
通讯作者:
F. Scatiggio;V. Tumiatti;R. Maina;M. Tumiatti;Massimo Pompili;R. Bartnikas
中科院分区:
文献类型:
--
作者:
F. Scatiggio;V. Tumiatti;R. Maina;M. Tumiatti;Massimo Pompili;R. Bartnikas
The nature and causes of corrosive sulfur induced failures are examined in oil-filled transformers and shunt reactors. Copper sulfide, which is formed when the corrosive sulfur in a mineral oil reacts with the copper conductors, is likely to diffuse into the paper tapes insulating the conductors. Since copper sulfide is partially conducting, the dielectric losses of the contaminated oil-impregnated-paper tapes are markedly increased; paper tapes in close proximity to the copper conductors are found to attain tan delta values > 1.0 even at room temperature. It is highly likely that thermal instabilities develop at those sites at operating temperatures, leading to increased loss currents and, ultimately, short circuits between the turns. This sequence of events is substantiated by evidence from the field, which indicates large areas of thermally degraded insulations and charred breakdown regions along the coils, the extent of which becomes more pronounced at higher operating temperatures (toward the top of the windings).