Noise levels in Johns Hopkins Hospital
Noise levels in Johns Hopkins Hospital
复制标题
DOI:
10.1121/1.2118327
复制
发表时间:
2005-12-01
影响因子:
2.4
通讯作者:
Chivukula, R
中科院分区:
文献类型:
--
作者:
Busch-Vishniac, IJ;West, JE;Chivukula, R
This article presents the results of a noise survey at Johns Hopkins Hospital in Baltimore, MD. Results include equivalent sound pressure levels (L-eq) as a function of location, frequency, and time of day. At all locations and all times of day, the L-eq indicate that a serious problem exists. No location is in compliance with current World Health Organization Guidelines, and a review of objective data indicates that this is true of hospitals throughout the world. Average equivalent sound levels are in the 50-60 dB(A) range for I min, 1/2, and 24 h averaging time periods. The spectra are generally flat over the 63-2000 Hz octave bands, with higher sound levels at lower frequencies, and a gradual roll off above 2000 Hz. Many units exhibit little if any reduction of sound levels in the nighttime. Data gathered at various hospitals over the last 45 years indicate a trend of increasing noise levels during daytime and nighttime hours. The implications of these results are significant for patients, visitors, and hospital staff. (c) 2005 Acoustical Society of America.