The optimal stack spacing for thermoacoustic refrigeration.
The optimal stack spacing for thermoacoustic refrigeration.
复制标题
热声制冷的最佳堆叠间距。
DOI:
--
复制
发表时间:
2002
影响因子:
2.4
通讯作者:
De Waele
中科院分区:
文献类型:
--
作者:
Meh Hassan Tijani;J. J. Zeegers;De Waele
The characteristic pore dimension in the stack is an important parameter in the design of thermoacoustic refrigerators. A quantitative experimental investigation into the effect of the pore dimensions on the performance of thermoacoustic devices is reported. Parallel-plate stacks with a plate spacing varying between 0.15 and 0.7 mm are manufactured and measured. The performance measurements show that a plate spacing in the stack of 0.25 mm (2.5 deltak) is optimum for the cooling power. A spacing of 0.4 mm (4 deltak) leads to the lowest temperature. The optimum spacing for the performance is about 0.3 mm (3 deltak). It is concluded that a plate spacing in the stack of about three times the penetration depth should be optimal (3 deltak) for thermoacoustic refrigeration.