Tower Surge Impedance
Tower Surge Impedance
复制标题
DOI:
10.1109/tpas.1969.292357
复制
发表时间:
1969
期刊:
影响因子:
--
通讯作者:
M. Sargent;M. Darveniza
中科院分区:
文献类型:
--
作者:
M. Sargent;M. Darveniza
Experimental and theoretical methods for determining the surge impedance of towers are presented. It is demonstrated that the values so obtained adequately describe the response of the tower when a transmission line is struck by lightning. A right cone representation for conventional double-circuit steel towers is proposed, and a theoretical analysis using field theory yields the surge impedance as Z= 60 ln (2/S) where S is the sine of the half-angle of the cone.