Study of Superconducting Fault Current Limiter Using Vacuum Interrupter Driven by Electromagnetic Repulsion Force for Commutating Switch
Study of Superconducting Fault Current Limiter Using Vacuum Interrupter Driven by Electromagnetic Repulsion Force for Commutating Switch
复制标题
DOI:
10.1109/tasc.2006.881809
复制
发表时间:
2006-12
影响因子:
1.8
通讯作者:
Iwao Shimizu;Yuji Naito;Iwao Yamaguchi;K. Kaiho;Hitoshi Mizoguchi;Satoru Yanabu
中科院分区:
文献类型:
--
作者:
Iwao Shimizu;Yuji Naito;Iwao Yamaguchi;K. Kaiho;Hitoshi Mizoguchi;Satoru Yanabu
Using a high-temperature superconductor, we constructed and tested a model superconducting fault current limiter (SFCL). The superconductor and the vacuum interrupter as the commutation switch were connected in parallel using a bypass coil. When the fault current flows in this equipment, the superconductor is quenched and the current is transferred to the parallel coil because of the voltage drop in the superconductor. This large current in the parallel coil actuates the magnetic repulsion mechanism of the vacuum interrupter. Due to the opening of the vacuum interrupter, the current in the superconductor is broken. By using this equipment, the current flow time in the superconductor can be easily minimized. On the other hand, the fault current is also easily limited by large reactance of the parallel coil