Single-Phase AC-AC Converter Operating as a Dynamic Voltage Restorer (DVR)
Single-Phase AC-AC Converter Operating as a Dynamic Voltage Restorer (DVR)
复制标题
作为动态电压恢复器 (DVR) 运行的单相 AC-AC 转换器
DOI:
10.1109/iecon.2006.347637
复制
发表时间:
2006
期刊:
影响因子:
--
通讯作者:
C. Nuñez
中科院分区:
文献类型:
--
作者:
J. Pérez;V. Cárdenas;L. Moran;C. Nuñez
This paper presents a single-phase AC-AC matrix converter which is able to compensate voltage harmonics and voltage regulation at critical loads terminals. The converter is composed with the minimum number of switching devices and is controlled using a non-linear law based on passivity achieving a high reliability and robustness during transient and steady state operation condition. The proposed scheme has the advantage that energy storage devices are not required. The converter is connected between the AC mains and the load through a series transformer. A DSP and a FPGA are used to program the passivity-based controller and to determine the state of the switches respectively. In this case, the converter is able to compensate up to 25% voltage sags and 50% voltage swells and to eliminate up to the fifteenth harmonic component. The tested system presents a fast time response and the stabilization time of the load voltage is less than 1 ms. Analysis and modeling as well as simulation and experimental results of a 5 kVA, 127 V, 60 Hz experimental setup are analyzed and presented