Identification of weak buses using Voltage Stability Indicator and its voltage profile improvement by using DSTATCOM in radial distribution systems
Identification of weak buses using Voltage Stability Indicator and its voltage profile improvement by using DSTATCOM in radial distribution systems
复制标题
使用电压稳定性指示器识别薄弱母线,并在放射状配电系统中使用 DSTATCOM 改善电压分布
DOI:
10.9790/1676-0241723
复制
发表时间:
2012
期刊:
影响因子:
--
通讯作者:
N. Visali
中科院分区:
文献类型:
--
作者:
S. Hussain;N. Visali
This paper presents a method to determine the weakest bus in a distribution network. The voltage stability indicator (VSI) identifies the weakest bus of system. The voltage stability indicator is derived from the voltage equation of radial distribution system. The weakest bus voltage profile is improved by placing a DSTATCOM. The DSTATCOM is modeled to supply the required reactive power for compensation and to maintain the voltage magnitude of the node where DSTATCOM is placed as 1 p.u. The validity of the proposed VSI and DSTATCOM modeling is examined by a standard 33 bus radial distribution system. The results validate the proposed VSI and DSTATCOM models in large distribution systems.