Diagnostic measurements of high voltage polymeric cable insulation

Diagnostic measurements of high voltage polymeric cable insulation
复制标题

高压聚合物电缆绝缘的诊断测量

DOI:
10.1109/iseim.1995.496500
复制
发表时间:
1995
期刊:
Proceedings of 1995 International Symposium on Electrical Insulating Materials
影响因子:
--
通讯作者:
S. Gubanski
S. Gubanski
中科院分区:
--
文献类型:
--
作者:
A. Bulinski;S. Bamji;E. So;G. Montanari;A. Motori;S. Gubanski

文献摘要

被引文献

相似文献

本文介绍了两种技术,可以帮助诊断聚合物电缆绝缘的工作条件。首先,氧化诱导时间(OIT)测量,需要获得绝缘样品并在实验室中进行测试。例如,可以在第一次电缆故障后采集绝缘样品。第二种技术,测量流经绝缘的电流交流损耗分量的谐波失真,可以发展成一种原位诊断技术。
This paper describes two techniques that can help to diagnose the operating conditions of polymeric cable insulation. The first, the oxidative induction time (OIT) measurements, requires obtaining specimens of the insulation and performing tests in a laboratory. Insulation samples can be taken, for example, after the first cable failure. The second technique, which measures the harmonic distortion of an ac loss component of the current flowing through the insulation, could evolve into an in situ diagnostic technique.