Partial discharge inception characteristics of LN/sub 2//polypropylene laminated paper composite insulation system for high temperature superconducting cables
Partial discharge inception characteristics of LN/sub 2//polypropylene laminated paper composite insulation system for high temperature superconducting cables
复制标题
高温超导电缆LN/sub 2//聚丙烯层压纸复合绝缘系统的局部放电起始特性
DOI:
10.1109/tdei.2005.1394027
复制
发表时间:
2005
影响因子:
3.1
通讯作者:
H. Okubo
中科院分区:
文献类型:
--
作者:
N. Hayakawa;T. Kobayashi;M. Hazeyama;T. Takahashi;K. Yasuda;H. Okubo
Partial discharge (PD) inception characteristics of liquid nitrogen (LN2)/polypropylene (PP) laminated paper composite insulation system for high temperature superconducting (HTS) cables were investigated in terms of the volume effect and the V-t characteristics. The electrical and optical measurements of PD inception characteristics showed that initial PD could be generated between PP laminated paper layers, as well as in a butt gap. Using a parameter called statistically stressed liquid volume (SSLV) based on the discharge probability in both butt gaps and LN2-filled thin layers between PP laminated papers, we could systematically analyze and evaluate the volume effect on PD inception stress (PDIE). Furthermore, experimental results revealed that n values of V-t characteristics at PD inception were as high as 80-110. On the other hand, the lower n values obtained at breakdown were interpreted by the intensified PD development in thermal bubbles generated after the PD inception