Harmonic interaction between large numbers of photovoltaic inverters and the distribution network
Harmonic interaction between large numbers of photovoltaic inverters and the distribution network
复制标题
DOI:
10.1109/ptc.2003.1304365
复制
发表时间:
2003-06
期刊:
影响因子:
--
通讯作者:
J. Enslin;W. Hulshorst;A.M.S. Atmadji;P. Heskes;A. Kotsopoulos;J. Cobben;P. van der Sluijs
中科院分区:
文献类型:
--
作者:
J. Enslin;W. Hulshorst;A.M.S. Atmadji;P. Heskes;A. Kotsopoulos;J. Cobben;P. van der Sluijs
The dominating mechanisms of interaction between large populations of PV inverters and the electrical distribution network are investigated. Some demonstration projects with large number of small PV-inverters in a low voltage network, show high levels of voltage distortion, although the emission level of an individual PV inverter satisfy the PQ standards. The main object of this paper is to analyse the observed phenomena of harmonic interference of large populations of inverters and provide some explanation of the resonance between existing network components and the PV inverters. These resonances may lie typically between the 5th and 40th harmonic number. The resonance phenomenon is investigated using extensive laboratory experiments on two inverter topologies, as well as computer modelling of different inverter topologies and network simulation studies on the Vroonermeer-Zuid network.