Locating sources of forced oscillations using transfer functions
Locating sources of forced oscillations using transfer functions
复制标题
DOI:
10.1109/peci.2017.7935743
复制
发表时间:
2017-02
期刊:
影响因子:
--
通讯作者:
N. Zhou;M. Ghorbaniparvar;S. Akhlaghi
中科院分区:
文献类型:
--
作者:
N. Zhou;M. Ghorbaniparvar;S. Akhlaghi
This paper proposes a transfer function method to locate sources of forced oscillations using phasor measurement unit (PMU) data. Forced oscillations herald problematic controls and device failure. They also incur stability concerns of power grid operators. To mitigate the negative impacts of forced oscillations, it is essential to locate their sources in time. This paper proposes a method to locate oscillation sources by building transfer functions between bus frequencies using PMU data. It is shown through analytical and simulation studies that the relative location of an oscillation source with respect to measurement points can be determined using the magnitude responses and phase responses of transfer functions. The proposed method does not heavily rely on a dynamic model and therefore is easy to implement and apply.