Application of an SVC to damp sub-synchronous interaction between wind farms and series compensated transmission lines
Application of an SVC to damp sub-synchronous interaction between wind farms and series compensated transmission lines
复制标题
DOI:
10.1109/pesgm.2012.6344797
复制
发表时间:
2012-07
期刊:
影响因子:
--
通讯作者:
D. Suriyaarachchi;U. Annakkage;C. Karawita;D. Kell;R. Mendis;R. Chopra
中科院分区:
文献类型:
--
作者:
D. Suriyaarachchi;U. Annakkage;C. Karawita;D. Kell;R. Mendis;R. Chopra
This paper demonstrates that wind farms connected to a grid through a series compensated transmission line may exhibit sub-synchronous oscillations. It is shown that the flux in the stator winding and the currents in the transmission line are the major participants of this mode. Dynamic Phasors are used to model the small signal model of the transmission network so that the network is accurately represented at sub-synchronous frequencies. An SVC is used to introduce damping to this oscillation mode, with line current as the feedback signal. The application is demonstrated for a large practical power system.