Initial transformer sizing for single-phase residential load
Initial transformer sizing for single-phase residential load
复制标题
单相住宅负载的初始变压器尺寸
DOI:
10.1109/tdc.1991.169521
复制
发表时间:
1991
期刊:
影响因子:
--
通讯作者:
R.F. Hoad
中科院分区:
文献类型:
--
作者:
K. Schneider;R.F. Hoad
A method for determining the correct economic size of distribution transformers using end-use appliance load profiles and the ANSI/IEEE Standard C57.91-1981 thermal model is described. The goal of this method is to minimize the cost of serving residential customers with electric power while maintaining high power quality and reliability. The three steps in determining the proper transformer size are given. Although applied only to single family and multifamily residential loads, the method can be extended to other types of load such as commercial or industrial.<<ETX>>