Low voltage and large current DC superconducting power cable designs for 10 km to 100km transmission line using experimental data of Ishikari project
Low voltage and large current DC superconducting power cable designs for 10 km to 100km transmission line using experimental data of Ishikari project
复制标题
利用石狩项目实验数据进行10km~100km输电线路低压大电流直流超导电缆设计
DOI:
10.1088/1742-6596/1293/1/012067
复制
发表时间:
2019
期刊:
影响因子:
--
通讯作者:
V. Sytnikov
中科院分区:
文献类型:
--
作者:
S. Yamaguchi;Takeo Yamada;T. Iitsuka;A. Sato;T. Sawamura;V. Sytnikov
Main merit of the DC superconducting power transmission line is low loss even in low voltage power transmission. It should be realized when the transmission length is long. Therefore, we discuss and analyse an aspect of thermo-hydrodynamic performance of Ishikari project, and show one design of 100 km transmission line. At the same time, we also discuss the cable design and the rated voltage of the cable is lower than 50 kV for 500MW transmission. This is one of the most important advantages to make the DC power grid because we can omit an ultra-high voltage substation, the primary and the secondary substations and we can connect the power stations to the distribution stations directly. Finally, we may be able to reduce the construction and operation costs of the power grid.