Direct Virtual Torque Control for Doubly Fed Induction Generator Grid Connection
Direct Virtual Torque Control for Doubly Fed Induction Generator Grid Connection
复制标题
DOI:
10.1109/tie.2009.2021590
复制
发表时间:
2009-04
影响因子:
7.7
通讯作者:
J. Arbi;M. J. Ghorbal;I. Slama-Belkhodja;L. Charaabi
中科院分区:
文献类型:
--
作者:
J. Arbi;M. J. Ghorbal;I. Slama-Belkhodja;L. Charaabi
This paper presents a grid-connection control strategy of doubly fed induction generator wind system based on the direct control of both a virtual torque and rotor flux of the generator. This control is achieved with no proportional-integral regulator and requires the measurement of only grid voltages, rotor currents, and rotor position. The same switching table is used for grid synchronization and for running process. A field-programmable-gate-array-based design of the proposed control is developed and tested on a 4-kW experimental prototype. Experimental results are provided to show the effectiveness of the fast and soft grid-connection method developed.