Optimal branch exchange for feeder reconfiguration in distribution networks
Optimal branch exchange for feeder reconfiguration in distribution networks
复制标题
用于配电网馈线重新配置的最佳支线交换
DOI:
10.1109/cdc.2013.6760333
复制
发表时间:
2013
期刊:
影响因子:
--
通讯作者:
S. Low
中科院分区:
文献类型:
--
作者:
Qiuyu Peng;S. Low
The feeder reconfiguration problem chooses the on/off status of the switches in a distribution network in order to minimize a certain cost such as power loss. It is a mixed integer nonlinear program and hence hard to solve. A popular heuristic search consists of repeated application of branch exchange, where some loads are transferred from one feeder to another feeder while maintaining the radial structure of the network, until no load transfer can further reduce the cost. Optimizing each branch exchange step is itself a mixed integer nonlinear program. In this paper we propose an efficient algorithm for optimizing a branch exchange step. It uses an AC power flow model and is based on the recently developed convex relaxation of optimal power flow. We provide a bound on the gap between the optimal cost and that of our solution. We prove that our algorithm is optimal when the voltage magnitudes are the same at all buses. We illustrate the effectiveness of our algorithm through the simulation of real-world distribution feeders.