Constrained Dynamic Matrix Control for a Boiler-Turbine Unit
Constrained Dynamic Matrix Control for a Boiler-Turbine Unit
复制标题
锅炉汽轮机组的约束动态矩阵控制
DOI:
10.1109/icmlc.2006.258396
复制
发表时间:
2006
期刊:
影响因子:
--
通讯作者:
Ji
中科院分区:
文献类型:
--
作者:
Zhijun Li;Zheng;W. Tan;Ji
A boiler-turbine unit is a typical multi-input multi-output (MIMO) industrial control system in power plant, which has nonlinear and couple characteristics. In this paper, a constrained dynamic matrix control (DMC) algorithm is designed for a nonlinear multivariable boiler-turbine unit with hard input constraints. Firstly an improved unconstrained DMC algorithm based on step response model for a single-input single-output (SISO) integrating process is proposed. It is shown that the proposed algorithm is more effective than conventional DMC and can also be extended to MIMO systems with integrating subsystems and input/output constraints. A 1-norm objective function is presented and the control actions can be obtained using linear programming online. Simulation results show that the designed control system has good tracking property and disturbance rejection ability without steady state offset while the control actions satisfy the constraints