6.6kV配电系统的电压畸变近年来一直在增加,特别是在商业领域。在超前功率因数条件下,系统阻抗与静态电容发生谐振,放大一定次数的谐波电流,产生电压畸变。 本文介绍了模型系统和实际系统的抑制效果试验结果。验证了有源电力滤波器对含电容系统谐振谐波的影响。
Voltage distortion of 6.6-kV distribution systems has been increasing recently especially in commercial areas. Harmonic currents of certain orders are amplified and voltage distortions are generated by the resonance between system impedance and static capacitor under the leading power factor condition. This paper describes the results of a test on suppression effects on model systems and an actual system. The effect of the use of an active power filter on the resonant harmonics of the system including capacitor was verified.