Feedback Linearization Control of Three-Phase UPS Inverter Systems
Feedback Linearization Control of Three-Phase UPS Inverter Systems
复制标题
DOI:
10.1109/tie.2009.2038404
复制
发表时间:
2010-01
影响因子:
7.7
通讯作者:
Dong-Eok Kim;Dong-Choon Lee
中科院分区:
文献类型:
--
作者:
Dong-Eok Kim;Dong-Choon Lee
In this paper, a feedback linearization technique is proposed to control the output voltage control of three-phase uninterruptible power supply systems. First, a nonlinear model including the output LC filters is derived from the power balance condition between the inverter output terminal and the load side. Then, input-output feedback linearization is applied to the nonlinear model to make it linear. The controller of the linearized model is designed by linear control theory. The tracking control law is obtained with a pole placement technique. It is shown experimentally that the proposed control scheme gives high dynamic responses in response to load variation as well as a zero steady-state error.