Feedback Linearization Control of Three-Phase UPS Inverter Systems

Feedback Linearization Control of Three-Phase UPS Inverter Systems
复制标题

DOI:
10.1109/tie.2009.2038404
复制
发表时间:
2010-01
影响因子:
7.7
通讯作者:
Dong-Eok Kim;Dong-Choon Lee
Dong-Eok Kim;Dong-Choon Lee
中科院分区:
计算机科学1区
文献类型:
--
作者:
Dong-Eok Kim;Dong-Choon Lee

文献摘要

被引文献

相似文献

本文提出了一种反馈线性化技术来控制三相不间断电源系统的输出电压控制。首先,从逆变器输出端和负载侧之间的功率平衡条件导出包括输出LC滤波器的非线性模型。然后,输入输出反馈线性化应用到非线性模型,使其线性化。利用线性控制理论设计了线性化模型的控制器。跟踪控制律的极点配置技术获得。实验结果表明,所提出的控制方案给出了高的动态响应,负载变化以及零稳态误差。
In this paper, a feedback linearization technique is proposed to control the output voltage control of three-phase uninterruptible power supply systems. First, a nonlinear model including the output LC filters is derived from the power balance condition between the inverter output terminal and the load side. Then, input-output feedback linearization is applied to the nonlinear model to make it linear. The controller of the linearized model is designed by linear control theory. The tracking control law is obtained with a pole placement technique. It is shown experimentally that the proposed control scheme gives high dynamic responses in response to load variation as well as a zero steady-state error.