Improving ducting to increase cooling performance of high-end web servers subjected to significant thermal shadowing – an experimental and computational study
Improving ducting to increase cooling performance of high-end web servers subjected to significant thermal shadowing – an experimental and computational study
复制标题
改进管道以提高遭受严重热阴影的高端网络服务器的冷却性能 - 一项实验和计算研究
DOI:
10.1109/semi-therm.2015.7100180
复制
发表时间:
2015
期刊:
影响因子:
--
通讯作者:
V. Mulay
中科院分区:
文献类型:
--
作者:
Divya Mani;J. Fernandes;R. Eiland;D. Agonafer;V. Mulay
A critical requirement in implementation of air cooling for rack mount servers is management of airflow to ensure that all components, especially critical devices such as CPUs, receive adequate flow as per requirement. In addition, component locations within the chassis play a vital role in passage of airflow and affect the overall system resistance. In this paper, sizeable improvement in chassis ducting is targeted to counteract effects of thermal shadowing in a dual-socket Open Compute web server wherein a CPU is located directly downstream from another. An experimentally-calibrated detailed CFD model of the server is deployed to parameterize design and location of the duct with the objective of understanding the effect of flow bypass on CPU die temperatures and fan power consumption. Enhancements achieved are tested experimentally by constructing a prototype of the improved chassis and reported with 23.4-39.6% savings in fan power consumption, 21.6-26% reduction in fan speeds, and 31.3-37.3% savings in flow rate required by the server. 6.4% to 16.7% reduction in acoustics noise levels caused by server fans is also presented.