A simplified model of heat and moisture transfer for tailrace tunnel ventilating in hydropower station
A simplified model of heat and moisture transfer for tailrace tunnel ventilating in hydropower station
复制标题
DOI:
10.1016/j.applthermaleng.2009.04.032
复制
发表时间:
2009-10
影响因子:
6.4
通讯作者:
Yanshun Yu;Xianting Li;W. Shi
中科院分区:
文献类型:
--
作者:
Yanshun Yu;Xianting Li;W. Shi
Tailrace tunnel ventilating can be used as a highly efficient and energy saving air conditioning for factory buildings in hydropower stations. This paper describes a simplified model of heat and moisture transfer for tailrace tunnel ventilating system with the assumption of isothermal boundary for tunnel wall, and constructs a small-scale experimental set-up to simulate the heat and moisture transfer process during the air flowing through the tunnel. The model has been validated against the experimental and field-test data, and it shows a good agreement. This simplified model is intended for use in annual performances prediction of heat and moisture transfer or provides the design tools for tailrace tunnel ventilating system in hydropower stations.