Insulation fault detection circuit for ungrounded DC power supply systems
Insulation fault detection circuit for ungrounded DC power supply systems
复制标题
DOI:
10.1109/icsens.2012.6411550
复制
发表时间:
2012-10
期刊:
影响因子:
--
通讯作者:
Yow-Chyi Liu;Chen-You Lin
中科院分区:
文献类型:
--
作者:
Yow-Chyi Liu;Chen-You Lin
This paper proposes a novel online insulation fault detection circuit to overcome the shortcomings of ungrounded DC power supply system for being unable to provide high sensitivity leakage current detection. In this paper, the capacitor group is used to connect with positive and negative bus and ground the intermediate point of the capacitor group, and that each branch loop is installed with a leakage current detection device. When insulation fault occur in the system, the capacitor is able to provide a leakage current return path and discharge through the stored energy in the capacitor. This will allow the Hall effect current sensor to detect the difference of positive and negative bus current, and deliver warning signal or control the breaker to cut off the power supply. The experiment result demonstrates that this novel method is able to detect 1mA/50kΩ insulation fault to achieve the high sensitivity detection goal.