Advanced RTDS-based studies of the impact of STATCOM on feeder distance protection
Advanced RTDS-based studies of the impact of STATCOM on feeder distance protection
复制标题
基于 RTDS 的 STATCOM 对馈线距离保护影响的高级研究
DOI:
10.1049/joe.2018.0179
复制
发表时间:
2018
影响因子:
--
通讯作者:
Guan R
中科院分区:
文献类型:
--
作者:
Guan R
The studies of the performance of feeder distance protection with multiple installations of the static synchronous compensator (STATCOM) are presented. Detailed representation of delta‐connected multi‐level modular converter (MMC) STATCOM is modelled and its impact on feeder distance protection is analytically studied. A real‐time digital simulation (RTDS) based hardware‐in‐the‐loop testing platform is established using practical distance relays, multiple detailed MMC STATCOM models and realistic transmission data. Different types of internal/external faults at varying locations are simulated to investigate the STATCOM's impact on feeder distance protection.