Transient Stability of Power Systems Integrated With Inverter-Based Generation

Transient Stability of Power Systems Integrated With Inverter-Based Generation
复制标题

DOI:
10.1109/tpwrs.2020.3033468
复制
发表时间:
2020-06
影响因子:
6.6
通讯作者:
Xiuqiang He;H. Geng
Xiuqiang He;H. Geng
中科院分区:
工程技术1区
文献类型:
--
作者:
Xiuqiang He;H. Geng

文献摘要

相似文献

传统电力系统暂态稳定的基本机制可以通过同步发电机(SG)的转子摆动动力学来物理理解。影响暂态稳定性的基本因素是SG之间的功角关系。大量逆变器发电(IBG)集成到电力系统中不可避免地改变了原有的功率角关系,从而导致更加复杂的暂态稳定机制。在这封信中,分析研究了IBG对电力系统暂态稳定性的影响。结果表明,IBG的加入使原来的功角关系变成了非正弦曲线,并引入了对转子摆幅峰值的限制,从而给暂态稳定性带来了新的瓶颈。
The fundamental mechanism of transient stability of the conventional power system can be physically understood with the rotor swing dynamics of synchronous generators (SGs). The basic factor affecting the transient stability is the power-angle relationship among the SGs. The integration of a large number of inverter-based generations (IBGs) into the power system inevitably changes the original power-angle relationship, therefore leading to a more complicated transient stability mechanism. In this letter, the impact of IBG on the power system transient stability is analytically investigated. It is shown that the connection of IBG changes the original power-angle relationship into a nonsinusoidal curve, introduces a limit on the peak of the rotor swing, and therefore brings about a new bottleneck for the transient stability.