Start-up Behavior of a Miniature Loop Heat Pipe with Multiple Evaporators and Multiple Condensers
Start-up Behavior of a Miniature Loop Heat Pipe with Multiple Evaporators and Multiple Condensers
复制标题
DOI:
10.2514/6.2007-1213
复制
发表时间:
2007-01
期刊:
影响因子:
--
通讯作者:
H. Nagano;J. Ku
中科院分区:
文献类型:
--
作者:
H. Nagano;J. Ku
This paper presents the test results on start-up behaviors of a miniature loop heat pipe (MLHP) with two evaporators and two condensers. The MLHP start-up tests were conducted by varying the heat load to one or both evaporators, the condenser sink temperatures, and with or without compensation chamber (CC) temperature control. More than 90 start-up tests have been conducted in horizontal position, and all were successful. Test results showed robust start-ups of the MLHP with heat loads of 1W to 100W. Loop started as soon as the heat load was applied, without a large temperature overshoot. The efficacy and good repeatability of the start-ups with CC active temperature control by using thermoelectric converter (TEC) was demonstrated. The ability of the loop to start with parasitic heat gain caused by cooling the CC temperature below ambient temperature was also demonstrated.