Rapid prediction of exergy destruction in data centers due to airflow mixing
Rapid prediction of exergy destruction in data centers due to airflow mixing
复制标题
DOI:
10.1080/10407782.2016.1139984
复制
发表时间:
2016-01-01
影响因子:
2
通讯作者:
Wemhoff, Aaron P.
中科院分区:
文献类型:
--
作者:
Bhalerao, Anish;Fouladi, K.;Wemhoff, Aaron P.
A novel lumped parameter approach is introduced to predict data center exergy destruction due to airflow mixing, resulting in a speedup of several orders of magnitude compared to detailed computational fluid dynamics (CFD) simulations. Both lumped parameter and detailed CFD methods agree within 8.5% for 11 test cases on an example data center. A significant time-saving design strategy is also introduced using two detailed CFD simulations to predict bulk flow parameters, and then applying lumped parameter analysis on flow-independent design parameters. The strategy shows agreement within 0.39% when computer room air conditioner (CRAC) supply temperature is varied from 12-20 degrees C.