Measurements and analysis of temperature rise at electrodes of a vacuum interrupter for high current applications
Measurements and analysis of temperature rise at electrodes of a vacuum interrupter for high current applications
复制标题
高电流应用真空灭弧室电极温升的测量和分析
DOI:
10.1109/isdeiv.2002.1027398
复制
发表时间:
2002
期刊:
影响因子:
--
通讯作者:
M. Matsukawa
中科院分区:
文献类型:
--
作者:
Y. Yamano;S. Kobayashi;M. Matsukawa
High current switching technology is required for protection of large superconducting coil in the field of nuclear fusion research. The temperature rise of the contacts and temperature distribution along the current feeding electrodes were measured. The contact diameter was 25 mm, and the tested material was Cu-Cr with different mixing ratios. Effect of a heat pipe was investigated as well. Measurements revealed that for the heat pipe installed case the temperature at the contact reached about 130/spl deg/C after the current conducting test of 2000 A for 120 min, while for the no heat pipe case the temperature reached 185/spl deg/C.