Harmonic analysis in a power system with wind generation

Harmonic analysis in a power system with wind generation
复制标题

DOI:
10.1109/tpwrd.2005.864063
复制
发表时间:
2006-10
影响因子:
4.4
通讯作者:
S. Papathanassiou;M. Papadopoulos
S. Papathanassiou;M. Papadopoulos
中科院分区:
工程技术2区
文献类型:
--
作者:
S. Papathanassiou;M. Papadopoulos

文献摘要

被引文献

相似文献

变速风力涡轮机在网络中注入谐波电流,这可能潜在地产生电压失真问题。在本文中,一个10兆瓦的风力发电场,打算连接到一个网络与扩展的高压海底电缆线路的案例研究。首先,系统建模方法和谐波潮流计算进行了说明。然后,系统的谐波阻抗计算的各种配置和操作条件下,其主要特点进行了讨论。提供谐波潮流计算以指示潜在的电压失真问题。一个简化的方法,建议在相关的IEC出版物,适用于该系统,其结果进行比较的谐波潮流。还讨论了风电场内谐波电流的求和问题
Variable-speed wind turbines inject harmonic currents in the network, which may potentially create voltage distortion problems. In this paper, a case study is presented for a 10-MW wind farm, intended to be connected to a network with extended high-voltage submarine cable lines. First, the system modeling approach and the harmonic load-flow calculation is described. Then, the harmonic impedance of the system is calculated for a variety of configurations and operating conditions, and its main characteristics are discussed. Harmonic load-flow calculations are provided to indicate potential voltage distortion problems. A simplified methodology, suggested in relevant IEC publications, is applied to the system and its results are compared to those of the harmonic load flow. A discussion on the summation of harmonic currents within a wind farm is also included