Location of Multiple PD Sources on Distribution Lines by Measuring Emitted Pulse-Train Electromagnetic Waves (特集:電線・ケーブル分野の新技術)
Location of Multiple PD Sources on Distribution Lines by Measuring Emitted Pulse-Train Electromagnetic Waves (特集:電線・ケーブル分野の新技術)
复制标题
通过测量发射的脉冲串电磁波来定位配电线路上的多个局放源(专题:电线电缆领域的新技术)
DOI:
10.1541/ieejpes1990.120.11_1431
复制
发表时间:
2000
期刊:
影响因子:
--
通讯作者:
K. Matsuura
中科院分区:
文献类型:
--
作者:
A. Tungkanawanich;Z. Kawasaki;K. Matsuura
This paper presents a new system designed for locating multiple sources of partial discharge. The system employs a sequential triggering method which can detect many pulses or pulse-train electromagnetic waves emitted from partial discharge in one measurement. We utilize four VHF wideband antennas as electromagnetic sensors and calculate the time delay of arrival between them in order to locate PD sources in 3-D. With this technique, we can locate multiple sources based on the assumption that there is only one electromagnetic pulse contained in the detected time window of 2 μs or each time window indicates a signal from one source. The smoothed coherence transform is applied to improve the time delay estimation and compared with the standard cross correlation. The proposed system also enhances the reliability of the method because many pulses are analyzed. A field experiment was performed to evaluate the proposed system.